Victron Energy Non-UL Listed MultiPlus-II Inverter/ Chargers (3000VA-5000VA)


The MultiPlus-II as the name suggests, is a combined inverter and charger in one elegant package. Its many features include a true sine wave inverter, adaptive charging, hybrid PowerAssist technology, plus multiple system integration features.

PowerControl & PowerAssist- Yes (on L1 Input)

Transfer Switch- 50A

Maximum AC Input Current- 50A

INVERTER

DC Input Voltage Range:

  • 12/3000 = 9.5 - 17V
  • 24/300019V - 33V
  • 48/300038V - 66V

Output

  • Output Voltage- 120VAC ± 2%
  • Frequency- 60 Hz ± 0.1%

Cont. Output Power at 25°C³- 3000VA

Cont. Output Power at 25°C- 2400W

Cont. Output Power at 40°C- 2200W

Cont. Output Power at 65°C- 1700W

Peak Power- 5500W

Maximum Efficiency

  • 12/3000 = 93%
  • 24/3000 = 94%
  • 48/3000 = 95%

Zero Load Power

  • 12/3000 = 13W
  • 24/3000 = 13W
  • 48/3000 = 11W

Zero Load Power In AES Mode

  • 12/3000 = 9W
  • 24/3000 = 9W
  • 48/3000 = 7W

Zero Load Power In Search Mode

  • 12/3000 = 3W
  • 24/3000 = 3W
  • 48/3000 = 2W

CHARGER

AC Input

  • Input Voltage Range- 90 - 140VAC
  • Input Frequency- 45 - 65Hz

Charge Voltage 'Absorption' 

  • 12/3000 = 14.4V
  • 24/3000 = 28.8V
  • 48/3000 = 57.6V

Charge Voltage 'Float'

  • 12/3000 = 13.8V
  • 24/3000 = 27.6V
  • 48/3000 = 55.2V

Storage Mode

  • 12/3000 = 13.2V
  • 24/3000 = 26.4V
  • 48/3000 = 52.8V

Max Battery Charge Current

  • 12/3000 = 120A
  • 24/3000 = 70A
  • 48/3000 = 35A

Battery Temperature Sensor- YES

GENERAL

Auxiliary Output- 32A

External AC Current Sensor (Optional)- 100A

Programmable Relay- YES

Protection- a - g

VE.Bus Communication Port- For parallel, split phase, and three phase operation, remote monitoring and system integration

General Purpose Com. Port- Yes x2

Remote On - Off- YES

Operating Temperature Range- -40°F - 140°F (Fan assisted cooling)

Humidity (Non-Condensing)- Max 95%

ENCLOSURE

Material & Color- Steel, Blue RAL 5012

Protection Category- IP22

Battery-Connection- M8 Bolts

120V AC-Connection- 13mm (6AWG)

Weight- 42lb

Dimensions (HxWxD)

  • 12/3000 = 22.8" x 10.9" x 5.8"
  • 24/3000 = 21.1" x 10.9" x 5.8"
  • 48/3000 = 22.5" x 10.9" x 5.8"

STANDARDS

Listings (Only applies to the UL listed version)

  • 12/3000 = UL458
  • 24/3000 = UL458
  • 48/3000 = UL1741

Safety- EN-IEC 60335-1, EN-IEC 60335-2-29, CSA 22.2 107.1-16

Emission, Immunity- EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 6100-3-3, IEC 61000-6-1, IEC 6100-6-2, IEC 61000-6-3

1) Can be adjusted to 50Hz

2) Protection Key

A) Output Short Circuit

B) Overload

C) Battery Voltage to high

D) Battery Voltage to low

E) Temperature to high

F) 120VAC on inverter output

G) Input Voltage ripple to high

3) Non-linear load, crest factor 3:1

4) Up to 75°F ambient

5) Switches off when no external AC sources available

 6) Programmable relay which can be set for general alarm, DC under voltage or genset start/stop function. AC rating- 120V / 4A, DC rating 4A up to 35VDC, and 1A up to 60VDC

7) A.o. to communicate with  a Lithium-Ion Battery

8) Dimensions of the not UL1741 Certified model- 21.1" x 10.9" x 5.8"

PowerControl & PowerAssist- YES

Transfer Switch- 95A

Maximum AC Input Current- 95A

INVERTER

DC Input Voltage Range- 38 - 66V

Output

  • Output Voltage- 120VAC ± 2%
  • Frequency- 60Hz ± 0.1%

Cont. Output Power at 25°C³- 5000VA

Cont. Output Power at 25°C- 4000W

Cont. Output Power at 40°C- 3700W

Cont. Output Power at 65°C- 3000W

Peak Power- 9000W

Maximum Efficiency- 96%

Zero Load Power- 15W

Zero Load Power In AES Mode- 10W

Zero Load Power In Search Mode- 3W

CHARGER

AC Input

  • Input Voltage Range- 90-140VAC
  • Input Frequency- 45-65Hz

 Charge Voltage 'Absorption'- 57.6V

Charge Voltage 'Float'- 55.2V

Storage Mode- 52.8V

Max. Battery Charge Current- 70A

Battery Temperature Sensor- YES

GENERAL

Auxiliary Output- 48A

External AC  Current Sensor (Optional)- 100A

Programmable Relay- YES

Protection-  a - g

VE.Bus Communication Port- For parallel, split phase and three phase operation, remote monitoring and system integration

General Purpose Com. Port- Yes 2x

Remote On-Off- YES

Operating Temperature Range- -40°F - 140°F (Fan assisted cooling)

Humidity (Non-condensing)- Max 95%

ENCLOSURE

Material & Color- Steel, Blue RAL 5012

Protection Category- IP22

Battery-Connection- M8 Bolts

120V AC-Connection- 35mm (2AWG)

Weight- 71lb

Dimensions (HxWxD)- 26.6" x 13.0" x 6.5"

STANDARDS

Listings (Only applies to the UL listed version)- UL1741 Pending

Safety- EN-IEC 60335-1, EN-IEC 60335-2-29, CSA 22.2 107.1-16

Emission, Immunity- EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 6100-3-3, IEC 61000-6-1, IEC 6100-6-2, IEC 61000-6-3

1) Can be adjusted to 50Hz

2) Protection Key

A) Output Short Circuit

B) Overload

C) Battery Voltage to high

D) Battery Voltage to low

E) Temperature to high

F) 120VAC on inverter output

G) Input Voltage ripple to high

3) Non-linear load, crest factor 3:1

4) Up to 75°F ambient

5) Switches off when no external AC sources available

 6) Programmable relay which can be set for general alarm, DC under voltage or genset start/stop function. AC rating- 120V / 4A, DC rating 4A up to 35VDC, and 1A up to 60VDC

7) A.o. to communicate with  a Lithium-Ion Battery

8) Dimensions of the not UL1741 Certified model- 21.1" x 10.9" x 5.8"